Download detailed specifications for this product

Download PDF

CARBON MONOXIDE DETECTOR

CMD5B1 Series

.

  • Measurement - Electrochemical
  • Sample Method - Diffusion
  • Measurement Range - Analog: 0-300 ppm Modbus: 0-500 ppm
  • Accuracy - ± 5 ppm or ± 5% of reading (whichever is greater) @ 0-50°C (32-122°F), 15-95% RH
  • Agency Approvals - Sensor is UL Recognized for ANSI/UL-2034 and UL-2075, E240671
  • Operating Conditions - -20-50°C (-4-122°F), 15-95% RH,
  • Stability - < 5% signal loss/year
  • Response Time - < 35 seconds for 90% step change
  • Life Expectancy - 5-7 years in air
  • Typical Coverage Area - 700 m² (7500 ft²) or 15 m (50 ft) radius
  • Wiring Connections - Screw terminal block (14 to 22 AWG)
  • Dimensions - 71 w x 104 h x 46 d mm (2.8” x 4.1“ x 1.8”)
  • Enclosure - ABS - UL94-V, IP65 (NEMA 4X)

Applications

Industries

Customization

    Not Available

    Please choose from our customization options and enter under comments while inquiring about this product`