  1. The old relay based logic & panel was replaced by simple & compact PLC panel
  2. Frequent maintenance related issues were sorted out
  3. Reduction of wiring required for various interlocks
  4. Indication of all the field/process parameters at a glance on one single panel.
  5. Alarm annunciator on panel for critical alarms occurred in the field
  6. All operations of the field devices through operator station on Panel
  7. Addition/Deletion of interlocks made simple with the help of PLC software.



In the Phosphorus Pentasulphide Plant, Phosphorous and Sulphur were mixed in a predefined ratio in to one common reactor.


Initially Phosphorus and Sulphur were taken into their individual tanks from storage tanks. From these tanks, the chemicals were charged to a common reactor in a specific predetermined proportion. In the reactor the chemicals were mixed and heated to make the final product. This process was carried out in batches; the batch sizes determined by planned total output of product.


The proportion of chemicals was to be controlled by measuring the rate of sulphur flowing in and using that rate to control the flow of phosphorus via pumps, valves and logic based interlocks.


Since the plant was operated by an older, relay-based control system, it had maintenance issues. Frequent failure of the relays or relay contacts was causing increased downtime. Radix replaced the relay based system with a PLC panel. Radix built a control panel which housed Mitsubishi FX3U Series PLC with 96 I/Os, PID controllers, Process Indicators/Controllers and Isolators/Signal Repeaters. Pushbuttons allowed easy operation by the operator and Indicating Lamps displayed the state of operations within the system.


The field signals were hooked up to the PLC along with the signals from the controller for High/Low alarms. Control of Pump, Valves, Stirrers and Blowers was done with Interlocks.


Level and Temperature High/Low level alarms generated by the controllers were hooked up to the 12 window Alarm Annunciator while some signals were taken from Process Controllers relays.


Pushbuttons and Selector Switches enabled operation of Pumps, Valves, and Blowers, controlled through logic with a Mitsubishi PLC (FX3U Series).


The Radix PLC system controlled the operations of:


4 Pumps (2 Phosphorus and 2 Sulphur)

4 Valves (2 Phosphorus and 2 Sulphur)

1 Air Blower

1 Stirrer

Water Cooling Pump

Two identical systems/plants were there, a Distilled and an Undistilled system.

Read more
330x330

Cleanroom Monitoring - Products Used

Product Image
PID Temperature Controllers

Full-featured, Mid range, Value range, Economy Range, Flameproof range
Read More...

Product Image
Temperature Transmitters

2-wire temperature transmitters - Din rail, Flameproof, Head mount
Read More...

Product Image
Handheld Thermometers

Universal Digital Thermometer, Handheld Thermometer with PT100 RTD
Read More...

Product Image
Temperature/ Process Scanners

Full-featured, Mid range, Value range, Economy Range, Flameproof range
Read More...

Product Image
Thermocouples

Mineral Insulated, Industrial, Bayonet, Platinum-Rhodium, Banburry,.
Read More...

Product Image
Controllers and Indicators

RH+T Controller, Loop Powered Indicators
Read More...

Product Image
Dial Thermometers

Gas Filled, Liquid Filled and Bimetallic Thermometers
Read More...

Product Image
RTDs

Gas Filled, Liquid Filled and Bimetallic
Read More...

logo

loading