Download detailed specifications for this product

Download PDF

DH3 Differential Pressure Controller

Series AT2DH3

The ATEX approved Series AT2DH3 Digihelic® Differential Pressure Controller is a 3 in 1 instrument possessing a digital display gage, control relay switches, and a transmitter with current output. Combining these three features allows the reduction of several instruments with one product, saving inventory, installation time and money. The ATEX approved Digihelic® controller is the ideal instrument for hazardous area pressure, velocity and flow applications by allowing for the selection of pressure, velocity or volumetric flow operation in several commonly used engineering units. Two SPDT control relays with adjustable dead bands are provided along with a scalable 4 to 20 mA process output. In velocity or flow modes, a square root output is provided on the 4 to 20 mA signal to coincide with the actual flow curve. Flame-proof ATEX enclosures are available in aluminum and can include a glass window for viewing process information and set point status on digital display. 

  • Service: Air and non-combustible, compatible gases
  • Wetted Materials: Consult factory
  • Housing Material: Die cast aluminum case and bezel
  • Accuracy: < 5 in w.c. (except ±2.5 in w.c.): ±1%; All other ranges: ±0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up)
  • Stability: < ±1% per year
  • Pressure Limits: Ranges ? 2.5 in w.c.: 25 psi; ±2.5", 5 in w.c.: 5 psi; 10 in w.c.: 5 psi; 25 in w.c.: 5 psi; 50 in w.c.: 5 psi; 100 in w.c.: 9 psi
  • Temperature Limits: 32 to 140°F (0 to 60°C) Case: -58 to 140°F (-50 to 60°C) (Note: Product temperature limits differ from case)
  • Compensated Temperature Limits: 32 to 140°F (0 to 60°C)
  • Thermal Effects: 0.020%/°F (0.036/°C) from 77°F (25°C)
  • Power Requirements: 12 to 28 VDC, 12 to 28 VAC 50 to 400 Hz
  • Power Consumption: 3 VA max
  • Output Signal: 4 to 20 mA DC into 900 ohms max
  • Zero & Span Adjustments: Accessible via menus in safe zone only
  • Response Time: 250 ms (damping set to 1)
  • Display: Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status
  • Electrical Wiring: Screw terminal
  • Mounting Orientation: Mount unit in vertical plane
  • Dial Size: 5" (127 mm) OD x 3-1/8" (79.38 mm).

Applications

  • Humidity

Industries

Customization

    Not Available

    Please choose from our customization options and enter under comments while inquiring about this product`

Inquiry for

required after months
×

Email Details Of DH3 Differential Pressure Controller - Series AT2DH3



×